UniFi UPS tower beside the headline UniFi UPS 1.6.9: Check Your Shutdown Protection.

Ubiquiti released UniFi UPS 1.6.9 to the Official channel on November 5, 2026. The most useful changes concern shutdown signalling and battery-status reporting, particularly for businesses using Network UPS Tools, or NUT, to protect servers and storage.

What changes

According to the official release notes, this update:

  • Supports up to five simultaneous NUT clients.
  • Corrects missing forced-shutdown signalling when Safe Shutdown was armed and the UPS was on battery.
  • Fixes incorrect on-battery/calibration status on UPS Tower and UPS 2U, plus a static-IP issue that could interrupt communication with UniFi Network.
  • Corrects read-only NUT authentication and charging-status reporting on UPS 2U Pro.

These are useful improvements for installations where shutdown decisions depend on accurate UPS information. They do not replace testing of the connected equipment.

Check the NUT client too

The UPS sends status information, but the client must respond correctly and shut down its own workloads. A working monitoring dashboard alone does not establish that this will happen. NUT’s documentation explains the shutdown process.

There is a relevant client-side example. An October community report described an unexpected shutdown with upsmon 2.8.1. Ubiquiti’s response pointed to a later client fix. NUT’s own 2.8.2 release notes confirm a correction for calibration status remaining active and affecting shutdown decisions.

Check the client version and your operating-system vendor’s supported updates. This older report should not be treated as proof of a 1.6.9 problem, or a promise that one client update solves every shutdown issue.

Plan for possible interruption

During its August 2026 UPS 2U Pro review, StorageReview observed the outlets losing power during a firmware update. The review does not identify the firmware versions involved, so that result cannot establish how 1.6.9 behaves.

It is still a good reason to schedule supervised maintenance rather than assume an update will leave every connected device running.

Before and after updating

  1. Record the UPS model, firmware, NUT client versions and shutdown settings. Confirm current backups and agree on possible downtime.
  2. Use UniFi Site Manager’s Update Manager to review the available update. Device release settings are managed within the associated application. Follow Ubiquiti’s update guide and select firmware offered for your hardware.
  3. Afterward, confirm that the UPS and intended clients reconnect and report sensible power and battery states.
  4. Arrange a controlled shutdown and recovery test. Allow enough time for databases, virtual machines and storage workloads to close safely, and verify how equipment restarts when power returns.

The rollout is gradual, and the release notes do not specify a universal minimum Network version. Check requirements for your exact model. We have not independently tested 1.6.9.